Enforcement details
- Reference
- ENF-003780-23122025
- Record type
- Notice
- Action date
- 25 November 2025
- Result or notice type
- Improvement notice
- Offence or breach
- You have failed to ensure that the low voltage electrical system at your premises has been constructed and maintained in a condition to prevent, so far as is reasonably practicable, danger. In particular, a number of 230-volt cables supplying your lights and sockets, the 400-volt power washing equipment, and 400 volt sockets around the site were not suitably constructed in order to prevent danger. The main distribution board had no suitably rated residual current protection. You were also unable to provide evidence to demonstrate that your installation was being maintained in a suitable and sufficient condition. Compliance Date: 2025-12-19 Result: Complied With Acts or Regulations Breached: Electricity at Work Regulations 1989, 3 / 1(a)
- Offence address
- Ely Road, Cardiff, CF5, Wales
- Region
- Wales
- Local authority
- Cardiff UA
- Industry
- Services
- Main activity
- 81299 - Other cleaning services
- Type of location
- Fixed
!