Enforcement details
- Reference
- ENF-003306-24102025
- Record type
- Notice
- Action date
- 16 October 2025
- Result or notice type
- Prohibition Notice Immediate
- Offence or breach
- Prohibits spraying of flammable vehicle coatings in the spray room. As spray paint mist made up of flammable coatings and flammable vapours are at risk of being ignited by unsuitable e.g., non ATEX rated electrical equipment and fixed wiring e.g., standard plugs, which can lead to a fire and potentially an explosion. Because as an employer you have failed to ensure that the risk from flammable atmospheres is either eliminated or reduced so far as is reasonably practicable, such as by providing a spray booth or room which features electrical equipment which is intrinsically safe e.g., ATEX rated. Acts or Regulations Breached: Dangerous Substances and Explosive Atmospheres Regulations 2002, 6 / 1
- Offence address
- Unit 2, 47A Scotts Road, Southall, London, UB2 5DD, England
- Recipient postcode
- UB2 5DD
- Region
- London
- Local authority
- Ealing
- Industry
- Services
- Main activity
- 96090 - Other service activities n.e.c.
- Type of location